905 King St

Welcome to 905 King. This emerging carrier hotel is the ideal location for customers who want to be near the downtown core with ample parking and easy access – without sacrificing the fastest connectivity and direct dedicated access to 151 Front. Beanfield’s private fibre-optic network connects 905 King to 151 Front over a high capacity ring, providing customers with direct access to any carrier in either Meet Me Room at 151 Front via a simple cross-connect. Like all our data centres, 905 King features redundant cooling and power, location security, fire protection and multiple proprietary redundant fibre-optic entrances.
For information on the building, the Beanfield colocation facility or the fibre-optic routing, see the downloadable spec sheets for more details.
Building Stacking Plan
Building Fibre Plan
Building Image
Building Image
Building Highlights
Building Overview
  • Year built: 1988 (Data Centre built in 2014)
  • Number of floors: 7 floors
  • Structure type: Concrete & Steel
  • Seismic Rating: UBC Seismic Zone zero
  • Ceiling Clearance (facility): 13’ 8”
  • Size: 112,000 Sq. Ft.
  • Data Center space: 60,000 Sq. Ft.
  • Meet-Me-Rooms: Two Meet-Me-Rooms served by diverse conduits banks to maintain full diversity of all fibre runs
  • Freight elevator: 10’ Height clearance
  • Access: Easily accessible with large loading dock area that is on a side street away from traffic
Power
  • 10 MVA, 2 pilot wire feed from Ontario Hydro via the Strachan Substation (approx. 900 meters away)
  • An additional 2 pilot wire feed from the Strachan Substation is planned for 2015 (will then total (x2) 2 pilot wire feeds with additional power capacity)
  • 7.7 MW of critical power
  • N+1 backup power generation
  • 11 Diesel generators on site
  • Generators consist of (x8) 400KW, (x1) 800KW, and (x2) 1600KW units
  • Ten seconds to transfer critical load from utility to the generators
  • 26,000 Liter main fuel storage tanks
Connectivity
  • Direct connection (12.25 microseconds) to 151 Front Street West via diverse high count fibre-paths
Fire Suppression
  • Wet pipe fire suppression system is installed in the main electrical room(s)
  • Dry pre-action fire suppression system is installed in the generator room(s)
  • Dry type of transformer used
Cooling
  • N+1 chilled water production + 2N cooling towers (two hour makeup water storage)
  • Domestic cold water storage = eight hours
  • Redundant power and chilled water distribution
  • Total mechanical cooling capacity for the site is 2,000 Tons (additional capacity planned)
Beanfield Facility Highlights
Facility
  • 3,000 sq. ft. initial (can be expanded to 10,000 sq. ft.)
  • 24” Anti-static raised flooring system
  • No cabling under raised flooring (chiller lines only)
  • Multi zone water sensors (including under raised flooring)
  • Overhead 3-tiered cable management system for power, fibre, and copper cabling
Security
  • 24/7 Security at main entrance with mantrap
  • 100% covered by low light CCTV (footage monitored and kept for ninety days)
  • e-Data card reader system with HID cards, and retina scanner
Space
  • 3,000 sq. ft. initial (can be expanded to 10,000 sq. ft.)
  • 24” Anti-static raised flooring system
  • No cabling under raised flooring (chiller lines only)
  • Multi zone water sensors (including under raised flooring)
  • Overhead 3-tiered cable management system for power, fibre, and copper cabling
Fire
  • Novec 1230 clean agent system
  • ASD-640 Air sampling system with four alarm levels
Cooling
  • N+1 Redundancy
  • CRAC units installed as per demand, capacity to 400 tons
  • Multiple 20-Ton Stultz CRAC units with redundant computer controlled compressors and humidity control systems
  • Triple Redundant Cooling (two chiller systems + our CRAC units are capable of individual cooling with internal compressors)
  • Hot aisle - cold aisle configuration with under floor cooling
Power
  • Dual utility feeds (see “Building Highlight” specs for details)
  • N+1 Redundant UPS systems (dual 450KVA Expandable Eaton UPS's)
  • N+1 Redundant generators (see "Building Highlights" sheet for details)
  • Schneider ATS with maintenance bypass (web enabled for monitoring)
  • Average allowance of 4KW of power per rack (more available upon request)
Connectivity
  • Diverse high count fibre cables coming into different locations within the suite via different entrances, and connecting back to diverse Meet Me Rooms in the building
  • Access to every carrier in either Meet Me Room of 905 King Street West
  • 100% diverse feeds to 151 Front Street West (with options of four different entrances into 151 Front Street West)
  • Access to every carrier in either Meet Me Room of 151 Front Street West
  • Direct fibre access to any of Beanfield’s 400+ commercial On-Net buildings throughout Toronto and Montreal